- 56 -
Parameter Table
Parameter Parameter Name Setting Range Unit Default Commission
F3-05
Multi-point V/F
frequency 2 (F2)
F3-03 to F3-07 Hz 3.00 -
F3-06
Multi-point V/F voltage 2 (V2)
0.0 to 100.0 % 8.0 -
F3-07
Multi-point V/F
frequency 3 (F3)
F3-05 to rated motor frequency
(F1-04)
Hz 8.00 -
F3-08
Multi-point V/F voltage 3
(V3)
0.0 to 100.0 % 20.0 -
F3-09
V/F slip compensation
gain
0 to 200.0 % 0.0 -
F3-10 V/F over-excitation gain 0 to 200 % 0 -
F3-11
V/F oscillation
suppression gain
0 to 100 % 30 -
F3-13
Voltage source for V/F
separation
0 to 8 N.A 0 -
F3-14
Voltage digital setting
for V/F separation
0 to rated motor voltage V 0 -
F3-15
Voltage rise time of V/F
separation
0.0 to 1000.0 s 0.0 -
F3-18
Overcurrent stall
prevention current limit
(for V/F mode)
100 to 200 (% AC drive rated
current)
% 170 -
F3-19
Overcurrent stall
prevention enable (for V/F
mode)
0: Disable
1: Enable
N.A 1 -
F3-20
Overcurrent stall prevention
gain (for V/F mode)
0 to 100 N.A 20 -
F3-22
Overvoltage stall
prevention voltage limit
(for V/F or SVC)
650 to 800 V 770 -
F3-23
Overvoltage stall
prevention enable (for V/
F or SVC)
0: Disable
1: Enable
N.A 0 -
F3-24
Overvoltage stall
prevention frequency
gain (for V/F or SVC)
0 to 100 N.A 30 -
F3-25
Overvoltage stall
prevention voltage gain
(for V/F or SVC)
0 to 100 N.A 30 -