- 57 -
Parameter Table
Group F4: input terminals
Parameter Parameter Name Setting Range Unit Default Commission
F4-00
DI1 function selection
(Standard on-board)
0: No function
1: Forward RUN (FWD)
2: Reverse RUN (REV)
3: Three-line control
4: Jog Forward (FJOG)
5: Jog Reverse (RJOG)
6: Terminal UP
7: Terminal DOWN
8: IGBT Enable
9: Fault reset (RESET)
10: RUN Pause
11: Normally open (NO) input of
external fault
12: Multi-reference terminal 1
13: Multi-reference terminal 2
14: Multi-reference terminal 3
15: Multi-reference terminal 4
16: Terminal 1 for acceleration/
deceleration time selection
17: Terminal 2 for acceleration/
deceleration time selection
18: Frequency source switchover
19: UP and DOWN setting clear
(terminal, operating panel)
20: Command source switchover
terminal 1
21: Acceleration/Deceleration
prohibited
22: PID pause
23: PLC status reset
24: Swing pause
25: Counter input
26: Counter reset
27: Length count input
28: Length reset
29: Torque control prohibited
30: Pulse input (enabled only for
DI5)
31: Reserved
32: Immediate DC braking
33: Normally closed (NC) input
of external fault
34: Frequency modi󶍾cation
forbidden
35: Reverse PID action direction
36: External STOP terminal 1
N.A 1 -
F4-01
DI2 function selection
(Standard on-board)
N.A 2 -
F4-02
DI3 function selection
(Standard on-board)
N.A 12 -
F4-03
DI4 function selection
(Standard on-board)
N.A 13 -
F4-04
DI5 function selection
(Standard on-board)
N.A 14 -
F4-05
DI6 function selection
(On-board expansion
card)
N.A 0 8
F4-06
DI7 function selection
(On-board expansion
card)
N.A 0 15
F4-07
DI8 function selection
(On-board expansion
card)
N.A 0 -
F4-08
PTC function enable
(On-board expansion
card)
N.A 0 -