- 119 -
Setup
value
Function Description
pause parameters are all in the recorded status, such as PLC
parameter, swing frequency parameter and PID parameter.
After this signal disappears, the driver restores to the status
before stopping.
11
External fault
normally open
input
After the external fault signal is sent to the driver, the driver
reports fault and stops.
12 MS speed
terminal 1
13 MS terminal 2
14 MS peed
terminal 3
15 MS terminal 4
It can realize 16S speed through the combination of digital
status of these four terminals. Refer attached table 6-1 for
the MS speed function description.
16
Speed-up/spe
ed-down time
selection
terminal 1
17
Speed-up/spe
ed-down time
selection
terminal 2
It can select four types of Speed-up/speed-down time
through the combination of digital status of these two
terminals.
18
Frequency
source
switching
When the frequency source selection (F0-07) is set to 2, it
performs switching between main frequency source X and
auxiliary frequency source Y via this terminal.
When the frequency source selection (F0-07) is set to 3, it
performs switching between main frequency source X and
(main frequency X plus auxiliary frequency source Y) via
this terminal.
When the frequency source selection (F0-07) is set to 4, it
performs switching between auxiliary frequency source X
and (main frequency X plus auxiliary frequency source Y)
via this terminal.
19
UP and
DOWN setup
clear (terminal
and keyboard)
When the frequency reference is digital frequency
reference, this terminal can be used to clear the frequency
value modified by UP/DOWN and thus restore the
reference frequency to the setup value of F0-08.
20 Running When the command source (F0-02) is set to 1, it performs