Description of Function Codes
MD280 User Manual
- 116 -
Function Code Parameter Name Setting Range Default
F2-08 AI1 minimum input 0.00 V to F2-10 0.02 V
F2-09
Corresponding setting of AI1
minimum input
-100.00%–100.0% 0.0%
F2-10 $,PD[LPXPLQSXW F2-08 to 10.00 V 10.00 V
F2-11
Corresponding setting mode of
$,PD[LPXPLQSXW
0: F2-12
1: Determined by AI2
0
F2-12
Corresponding setting of AI1
PD[LPXPLQSXW
-100.00%–100.0% 100.0%
F2-13 $,¿OWHUWLPH 0.00–10.00s 0.10s
7KHVHSDUDPHWHUVDUHXVHGWRGH¿QHWKHUHODWLRQVKLSEHWZHHQWKHDQDORJLQSXWYROWDJHDQG
WKHFRUUHVSRQGLQJVHWWLQJ:KHQWKHDQDORJLQSXWYROWDJHH[FHHGVWKHPD[LPXPYDOXHWKH
PD[LPXPYDOXHLVXVHG:KHQWKHDQDORJLQSXWYROWDJHLVOHVVWKDQWKHPLQLPXPYDOXHWKH
minimum value is used.
When the analog input is current input, 1 mA current corresponds to 0.5 V voltage.
)$,¿OWHUWLPHLVXVHGWRVHWWKHVRIWZDUH¿OWHUWLPHRI$,,IWKHDQDORJLQSXWLVOLDEOH
to interference, increase the value of this parameter to stabilize the detected analog input.
+RZHYHULQFUHDVHRIWKH$,¿OWHUWLPHZLOOVORZWKH UHVSRQVHRIDQDORJGHWHFWLRQ6HWWKLV
parameter properly based on actual conditions.
In different applications, 100% of analog input corresponds to different nominal values. For
details, refer to the description of different applications.
Figure 6-8 Relationship between analog input and corresponding setting
Corresponding setting
such as frequency
and torque
AI
0.0%
0 V
0 mA
F2-12 AI2
F2-09
F2-08
F2-10
Function Code Parameter Name Setting Range Default
F2-14 AI2 minimum input 0.00 V to F2-16 0.02 V
F2-15 Corresponding setting of AI2
minimum input
-100.00%–100.0% 0.0%
F2-16 $,PD[LPXPLQSXW F2-14 to 10.00 V 10.00 V
F2-17
Corresponding setting mode of AI2
PD[LPXPLQSXW
0: F2-18
1: Determined by AI1
0
F2-18 Corresponding setting of AI2
PD[LPXPLQSXW
-100.00%–100.0% 100.0%
efesotomasyon.com