Operation and Display
MD280 User Manual
- 60 -
4.4.4 Timing Stop
The MD280 supports timing stop. The timing duration is set in F5-12; when it is set to 0, the
timing stop function is disabled. When F5-13 is set to 1, the AC drive automatically stops
when the accumulative running time reaches the set time.
Figure 4-11 Setting of the timing stop function
F5-12 0: timing function disabled
F5-12 1-65535 h: timing duration
Time t
Running command
Running state
Automatic stop
F5-13 1
0: Continue to run
1: Stop
F7-12 F5-12
F5-12
Timing duration
For more details, see the description of F5-12 and F5-13.
4.5 JOG Running
In certain applications, the AC drive needs to run at a low speed temporarily to facilitate
equipment test or other commissioning operations. In this case, you can set the AC drive to
perform JOG running.
Figure 4-12 JOG running
Running frequency f
Time t
Jog running
frequency F5-00
Jog
command
Jog acceleration
time F5-01
Jog deceleration
time F5-02
Ƶ
Parameter Setting and Operation of JOG Running in Operation Panel Control
Figure 4-13 JOG running in operation panel control
JOG
command key
MF.K
F7-15 3 F0-00 0
F5-00
JOG running frequency
F5-01
JOG acceleration time
F5-02
JOG deceleration time
Operation
panel control
Define the MF.K
key as the
"Forward JOG" key
Forward
JOG
stop state
JOG running
parameters
6HWWKHSDUDPHWHUVDFFRUGLQJWR WKHSUHFHGLQJ¿JXUH,QVWRSVWDWHRIWKH$&GULYHKROG
down
MF.K
, and the AC drive starts JOG running. After you release
MF.K
, the AC drive
decelerates to stop.