Description of Function Codes
MD280 User Manual
- 98 -
Chapter 6 Description of Function Codes
Group F0: Basic Parameters
Function Code Parameter Name Setting Range Default
F0-00
Command source
selection
0: Operation panel control
1: Terminal control
2: Communication control
0
It is used to determine the input channel of the AC drive control commands, such as run,
stop, forward rotation, reverse rotation and jog operation. You can input the commands in
the following three channels:
2SHUDWLRQSDQHOFRQWURO/2&$/5(027LQGLFDWRU2))
Commands are given by pressing key
RUN
,
MF.K
, or
STOP
RES
on the operation
panel.
7HUPLQDOFRQWURO/2&$/5(027LQGLFDWRU21
Commands are given by means of multifunctional input terminals with functions such
as FWD, REV, FJOG, and RJOG.
&RPPXQLFDWLRQFRQWURO/2&$/5(027LQGLFDWRUEOLQNLQJ
Commands are given from the host computer.
Function Code Parameter Name Setting Range Default
F0-01
Main frequency
source X selection
'LJLWDOVHWWLQJ83'2:1
PRGL¿FDWLRQ
1: AI1
2: AI2
3XOVHVHWWLQJ',
4: Multi-reference
5: Simple PLC
6: PID
$,$,
8: Communication setting
3,'$,
3,'$,
0
It is used to select the setting channel of the main frequency. You can set the main
frequency in the following 10 channels:
'LJLWDOVHWWLQJ83'2:1PRGL¿FDWLRQ
7KHLQLWLDOYDOXHRIWKHVHWIUHTXHQF\LVWKHYDOXHRI)3UHVHWIUHTXHQF\<RXFDQ