Operation and Display
MD280 User Manual
- 56 -
Function Code
Parameter
Name
Setting Range Default
F7-14
LED
display stop
parameters
1–511
7 6 5 4 3 2 1 0
Set frequency Hz
Bus voltage V
DI state
DO state
AI1 voltage V
AI2 voltage V
Counted value
Length value
15 14 13 12 11 10 9 8
Pulse frequency Hz
Reserved
51
When the AC drive is powered on again after power failure, the parameters that are selected
before power failure are displayed.
Select the required parameters by pressing
7KHIROORZLQJH[DPSOHVKRZVKRZWRVHW
F7-13 to display the running parameters on LED.
1 Assume that the following parameters need to be displayed:
Running frequency, bus voltage, output voltage, output current, output power, and PID
feedback
2 Set the corresponding bit of each parameter to be displayed to 1.
3 Convert the binary data to a decimal value, and set this value in F7-13.
7 6 5 4 3 2 1 0
Low bits
15 14 13 12 11 10 9 8
High bits
0011110100100000
2 0 3 D
Binary
+H[DGHFLPDO
F7-13
Decimal
2 [16³ 0 [16² 3 [16 13 8253
4.4 Starting or Stopping the AC Drive
4.4.1 Selecting the Start/Stop Command Source
There are three start/stop command sources, namely, operation panel control, terminal
control, and communication control. You can select the command source in F0-00.
Function
Code
Parameter
Name
Setting Range Description Default
F0-00
Command
source
selection
0: Operation panel
FRQWUROLQGLFDWRU2))
1: Terminal control
LQGLFDWRU21
2: Communication
FRQWUROLQGLFDWRU
EOLQNLQJ
Press
RUN
or
STOP
RES
to start or
stop the AC drive.
$',WHUPLQDOQHHGVWREHGH¿QHGDV
the run/stop terminal.
The Modbus-RTU communication
protocol is used.
0