MD280 User Manual Operation and Display
- 57 -
 0: Operation panel control
After you press
RUN
WKH$&GULYHVWDUWVUXQQLQJWKH581LQGLFDWRULV21$IWHU\RX
press
STOP
RES
ZKHQWKH$& GULYHLVLQUXQQLQJVWDWHWKH$&GULYHVWRSVUXQQLQJ WKH
581LQGLFDWRULV2))
 1: Terminal control
This control mode is applicable to scenarios where the DIP switch or electromagnetic
button is used to start or stop the application system or scenarios where the dry contact
signal is used to start or stop the AC drive.
The switch signal mode is set in F2-06. The input terminal of the start/stop signal is set
in F2-00 to F2-04. For details, see the description of F2-06 and F2-00 to F2-04.
([DPSOH
To use the DIP switch as the start/stop source, and allocate the forward rotation switch
signal to DI2 and the reverse rotation switch signal to DI3, perform the setting as shown
LQWKHIROORZLQJ¿JXUH
Figure 4-5 Setting of using the DIP switch for start/stop
.
1
2
.
.
F0-00 1
Running
command
F2-06 0
Control switch
Terminal
Function
code
Setting
value
Terminal
control
.
COM
RUN/
Forward
Forward RUN
Terminal control
Command source
selection
Two-line mode 1
RUN/
Reverse
Reverse RUN
SW2
SW1
F2-00
F2-01
F2-02
F2-03
F2-04
DI1
DI2
DI3
DI4
DI5
,QWKHSUHFHGLQJ¿JXUHZKHQ6:LV21WKH$&GULYHLQVWUXFWVIRUZDUGURWDWLRQZKHQ
SW1 is OFF, the AC drive stops. When SW2 is ON, the AC drive instructs reverse
running; when SW2 is OFF, the AC drive stops. If SW1 and SW2 are ON or OFF
simultaneously, the AC drive stops.
([DPSOH
To use the electromagnetic button as the start/stop source, and allocate the startup
signal to DI2, stop signal to DI3 and reverse rotation signal to DI4, perform the setting
DVVKRZQLQWKHIROORZLQJ¿JXUH
Figure 4-6 Setting of using the electromagnetic button for start/stop
.
.
1
2
3
.
F0-00 1
Running
command
F2-06 2
Control
button
Terminal
Function
code
Setting
value
Terminal
control
.
RUN/
Forward
STOP
Forward RUN
Stop
Terminal control
Command
source selection
Three-line mode 1
RUN/
Reverse
Reverse RUN
SB2
SB1
SB3
DI1
DI2
DI3
DI4
DI5
COM
F2-00
F2-01
F2-02
F2-03
F2-04