Chapter 1    Safety and Precautions 
 
-9- 
 
Please dispose the inverter as industrial 
wastes.  
1.2.13 Adaptable Motor 
1) The standard adaptable motor is 
four-pole squirrel-cage asynchronous 
induction motor.  If such motor is not 
available, be sure to select adaptable motors 
according to the rated current of the motor.  
In applications where drive permanent 
magnetic synchronous motor is required, 
please consult our company;   
2) The cooling fan and the rotor shaft of 
the non-variable-frequency motor adopt 
coaxial connection. When the rotating speed 
is reduced, the cooling effect will be reduced. 
Therefore, a powerful exhaust fan shall be 
installed, or the motor shall be replaced with 
variable-frequency motor to avoid the over 
heat of the motor.   
3) Since the inverter has built-in standard 
parameters of the adaptable motors, it is 
necessary to perform motor parameter 
identification or modify the default values so 
as to comply with the actual values as much 
as possible, or it may affect the running effect 
and protection performance;   
The short circuit of the cable or motor 
may cause alarm or explosion of the inverter.   
Therefore, please conduct insulation and 
short circuit test on the newly installed motor 
and cable. Such test shall also be conducted 
during routine maintenance.  Please note 
that the inverter and the test part shall be 
completely disconnected during the test.   
 
 
 