Chapter 5 Function Parameter Table 
 
-41- 
 
Chapter 5 Function Parameter Table
If FP-00 is set to non-zero value, it means parameter protection password is set, and the 
parameter menu cannot be opened until correct password is entered. To cancel the password, 
it needs to set FP-00 to “0”.   
The symbols of the function code are described as follows:   
 
“ż”: It indicates that the parameter setup value can be modified when the 
inverter is in stop status and running status. 
 
  “×”: It indicates that the parameter setup value cannot be modified when the inverter is in 
the running status.   
“*”it indicates the parameter is the actual tested value, which cannot be modified. 
“—”: It indicates this parameter is “Factory default parameter” and can be set only by the 
manufacturer.   
Function Parameter Table
Code  Name Setup range 
Minimum
unit
Factory 
default 
value
Cha-
nge 
  Group F0 Basic Function Group 
F0-00  Control mode 
0: None-speed sensor vector 
control (SVC) 
1: Reserved 
2: V/F control 
1  0  × 
F0-01 
Command Source 
Selection 
0: Operation panel running 
command channel (LED OFF) 
1: terminal operation command 
channel (LED ON) 
1  0  ż 
F0-02 
Frequency source 
selection 
0: Digital setup (without 
memory)   
1: Digital setup (with memory) 
2: Pulse setup (effective DI4 
input ) 
3: Al1 
4: Al2 
5: MS speed 
1  0  × 
 