Chapter 6 Parameter Description   
 
-59- 
 
1: Rotation speed tracking restart 
The inverter judges the rotation speed and 
direction of the motor firstly and then starts at 
the frequency of the tracked rotation speed of 
the motor. The rotating motor will be started 
smoothly without surge (The trace frequency 
is taken as frequency before stopping by 
default).   
It is applicable to the restart upon transient 
power failure of large loads.   
To ensure the performance of Rotation speed 
tracking restart, it needs to set the motor 
parameters accurately.    (Group F1) 
Stop
mode 
Factory 
default value
0 
0 
Deceleration to stop
F0-16 
Setup 
range 
1 
Coast to stop 
0: Deceleration to stop 
After the stop command is enabled, the 
inverter reduces the output frequency in 
accordance with the deceleration mode and 
the defined acceleration/deceleration time, 
and will stop after the frequency reduces to 
zero. 
 
1: Coast to stop 
After the stop command is enabled, the 
inverter will terminate the output immediately.   
The load will coast to stop according to the 
mechanical inertia.   
Group F1 Motor Parameters
Motor
type 
selection 
Factory 
default 
value 
0 
F1-00 
Setup 
range   
0 
common 
asynchronous 
motor   
1
Variable frequency 
asynchronous 
motor 
2
permenant 
magnetic 
synchronous 
motoU 
 
Rated
power 
Factory 
default 
value 
model 
dependent 
F1-01
Setup range :0.4kW 1000.0kW 
Rated
voltage
Factory 
default 
value 
380V 
F1-02
Setup range :0V440V 
Rated
current
Factory 
default 
value 
model 
dependent 
F1-03
Setup range :0.00A655.35A 
Rated
frequency
Factory 
default 
value 
50.00Hz 
F1-04
Setup range :0.00 to maximum 
output frequency 
Rated
Rotation
speed 
Factory 
default 
value 
1460rpm 
F1-05
Setup range :0rpm to 30,000rpm 
 
 
 