Chapter 1    Safety and Precautions 
 
-7- 
 
1.1.6 During the operation: 
Danger Danger 
1. Do not approach the mechanical 
equipment when selecting the restart 
function.  
Otherwise it may cause injury! 
2. Do not touch the heatsink fan or 
discharge resistor to sense the 
temperature.  Otherwise, you may get 
burnt! 
3. Detection of signals during the 
operation shall only be conducted by 
qualified technician. Otherwise, personal 
injury or equipment damage may be 
caused! 
NoteNote
 
4. During the operation of the inverter, 
keep items from falling into the 
equipment.  Otherwise, it may damage 
the equipment! 
5. Do not start and shut down the 
inverter by connecting and 
disconnecting the contactor.   
Otherwise, it may damage the 
equipment!
 
1.1.7 Maintenance
Danger Danger 
1. Do not repair and maintain the 
equipment with power connection.  
Otherwise there will be danger of 
electric shock! 
2. Conduct repair and maintenance 
after ensuring that the charge LED 
indictor of the inverter is OFF.  
Otherwise, the residual charge on the 
capacitor may cause personal injury! 
3. The repair and maintenance for 
inverter can only be performed by 
professional technicians.   
  Otherwise, it may cause personal 
injury or equipment damage! 
1.2 Precautions 
1.2.1 Motor Insulation Inspection 
When the motor is used for the first time, 
or when the motor is reused since the 
previous use, or when periodical inspection is 
performed, the motor insulation inspection 
shall be performed so as to avoid damaging of 
the inverter due to the insulation failure of the 
motor windings.    The motor wires must be 
disconnected from the inverter during the 
insulation inspection. It is recommended to 
use the 500V megameter, and the insulating 
resistance measured shall be at least 5Mȍ.  
1.2.2 Thermal Protection of the Motor   
If the ratings of the motor do not match 
those of the inverter, especially when the 
rated power of the inverter is higher than the 
rated power of the motor, the relevant motor 
protection parameters in the inverter shall be 
adjusted, or thermal relay shall be mounted to 
protect the motor.   
1.2.3 Running with Frequency higher than 
Standard Frequency 
This inverter can provide output 
frequency of 0Hz to 300Hz.    If the user needs 
to run the inverter with frequency of more than 
50Hz, please take the resistant pressure of 
 