Chapter 4 Operation and Display 
 
-39- 
 
Note: When operating on level 3 menu, 
press PRG key or ENTER key to return to 
level 2 menu.  The difference between PRG 
key and ENTER key is described as follows: 
Pressing ENTER KEY will save the setup 
parameter to control board and return to the 
level 2 menu and automatically shift to the 
next function code, while pressing PRG key 
will directly return to level 2 menu without 
saving the parameter, and it will return to the 
current function code.   
Example: Modify the function code F2-05 
from 10.00Hz to 15.00Hz. (Characters in bold 
shows the flashing) 
 
Fig.4-3 Example of parameter editing 
operation  
In level 3 menu, if the parameter has no 
flashing bit, it indicates that the function code 
cannot be modified. The possible reasons 
include:  
1) The function code is an 
unchangeable parameter, such as actual 
detection parameter, running record 
parameter, etc.   
2) The function code cannot be 
modified in running status. It can be 
modified only after the unit is stopped.   
4.3 Method of Viewing Status 
Parameter
 For MD300 inverter, under the stop or 
operating status, the status parameters of the 
inverter can be displayed by LED digital tube. 
The status parameters under the stop/running 
statuses can be cyclically displayed through 
pressing shift key.  Under the stop status, 
there are five status parameters of MD300 
inverter can be displayed cyclically through 
shift key, they are as follows: setup frequency, 
bus voltage, DI input status, analog input AI1 
voltage and analog input AI2 voltage.
 
Under the running status, there are seven 
status parameters of MD300 inverter can be 
displayed cyclically through shift key, they are 
as follows: setup frequency, bus voltage, 
output voltage, output current, DI input status, 
analog input AI1 voltage and analog input AI2 
voltage. 
Show the terminal status (displayed in 
decimal system) in accordance with bit, that is 
BIT0 refers to 1, showing effective DI1 input   
BIT1 refers to 1, showing effective DI2 input   
BIT2 refers to 1, showing effective DI3 input   
BIT3 refers to 1, showing effective DI4 input   
BIT4 to BIT5: retained 
BIT6 refers to 1, showing effective RELAY 
output   
BIT7 refers to 1, showing effective DO output   
When the inverter is restarted upon power 
shutdown, the displayed parameters are the 
parameters selected before the power 
shutdown.   
4.4 Password Setting 
The inverter provides user password 
protection function. When FP-00 is set to 
non-zero value, it indicates the user password, 
and the password protection turns valid after 
exiting from the function code editing status. 
When pressing PRG key again, “------“will be 
displayed, and common menu cannot be 
 
efesotomasyon.com