Chapter 6 Parameter Description   
 
-64- 
 
2: Three-line running mode : In this mode, Dln 
is enabled terminal, and the direction is 
controlled by FWD and REV respectively.   
However, the pulse is enabled through 
disconnecting the signal of Dln terminal when 
the inverter stops.   
 
Fig.6-4 Three-line Running Mode 
Where,   
SB1 Stop button    SB2: FWD button   
SB3: REV button 
Din is the multifunctional input terminal of DI1 
to DI4. In this case, the function of the 
corresponding terminal shall be defined as 
“three-line running control”. 
Prompt: For two-line operation mode, when 
FWD/REV terminals are enabled and the 
inverter stops due to the command from other 
sources, the inverter will not operates after the 
canceling of the stop command even though 
the control terminals FWD/REV are still 
enabled. Retrigger FWD/REV will make the 
inverter run. Such as the valid STOP key in 
the operation command channel (See F6-12).
 
However, if the inverter stops when fault alarm 
occurs, the running of the inverter is controlled 
by function code F6-09. 
Terminal 
UP/DOWN
Speed 
Factory 
default 
value 
1.00 
Hz/s 
F3-01 
Setup 
range 
0.01Hz/s100.00Hz/s 
Terminals UP/DOWN is used to adjust the 
change rate when setting the frequency.   
AI 
minimum
input 
Factory 
default 
value 
0.00V 
F3-02
Setup range 
0.0010.00V 
AI 
minimum
input 
correspon
ding setup
Factory 
default 
value 
0.0% 
F3-03
Setup range 
-100.0%100.0% 
AI middle 1 
input
Factory 
default 
value 
5.00V 
F3-04
Setup range 
0.00V10.00V 
AI middle 1 
input 
correspon
ding setup
Factory 
default 
value 
50.0% 
F3-05
Setup range 
-100.0%100.0% 
AI middle 2 
input
Factory 
default 
value 
8.00V 
F3-06
Setup range 
0.00V10.00V 
AI middle 2 
input 
correspon
ding setup
Factory 
default 
value 
80.0% 
F3-07
Setup range 
-100.0%100.0% 
AI 
maximum
input 
Factory 
default 
value 
10.00
V 
F3-08
Setup range 
0.00V10.00V 
 