Chapter 6 Parameter Description
-68-
Stall gain
over current
Factory
default
value
20
F5-04
Setup
range˖
0100
It adjusts the inverter’s
capacity in suppressing
the stall over current.
The bigger the value is,
the stronger the
suppressing capacity is.
For the load with small
inertia, the value should
be small. Otherwise,
the dynamic response
of the system will be
slow. For the load with
large inertia, the value
should be large.
Otherwise, the
suppressing result will
be poor, and over
current fault may occur.
Fault auto
reset times
Factory
default
value
0
F5-06
Setup
range˖
03
When the inverter
selects fault auto reset,
it is used to set the
times of auto reset. If
this value is exceeded,
the inverter will stop
because of failure and
wait for maintenance.
Fault auto
reset
interval
Factory
default
value
1.0s
F5-07
Setup range˖
0.1s 100.0s
Select time
interval
between fault
occurring and
automatic reset
Input phase
loss
protection
selection
Factory
default
value
1
F5-08
Setup
range˖
0: Disabled
1: Enabled
Select whether to
provide protection
for input phase
loss. Only the
MD series inverter
over 18.5kW can
have input phase
loss protection
function, and the
inverter below
18.5kW has not
such function no
matter whether F5-
8 is set to 0 or 1.