Technical Data
‑134‑
Table 7–3 Electrical specifications (three‑phase 380 V to 480 V) (T5 to T6 models)
Item
Specifications
Model: MD500Txxxxx‑PLUS
18.5G/
22P(B)
22G/30P(B)
18.5G/
22P(B)‑T
22G/
30P(B)‑T
30G/37P(B) 37G/45P(B)
Structure T5 T6
Output
Power (kW) (heavy load)
18.5 22 18.5 22 30 37
Power (kW) (light load)
22 30 22 30 37 45
Rated output current (A)
(heavy load)
37 45 37 45 60 75
Rated output current (A)
(light load)
45 60 45 60 75 91
Output voltage Three‑phase 0 V to input voltage
Max. output frequency 599 Hz (editable through a parameter)
Carrier frequency 0.8 kHz to 8.0 kHz (automatically adjusted according to the load characteristics)
Overload capacity
Heavy load (G‑type AC drive): 150% for 60s with rated current
Light load (P‑type AC drive): 110% for 60s with rated current
Input
Rated input current (A)
(heavy load)
49.5 59 43.4 51.3 57 69
Rated input current (A)
(light load)
59 65.8 51.3 65.8 71 86
Rated voltage/frequency Three‑phase 380 VAC to 480 VAC, 50/60 Hz
Voltage range
Allowable fluctuation: –15% to +10% (323 VAC to 528 VAC)
Frequency range
Allowable fluctuation: ±5% (47.5 Hz to 63 Hz)
Power capacity (kVA)
(heavy load)
45 54 45 54 52 63
Power capacity (kVA)
(light load)
54 60 54 60 65 79
Thermal
design
Thermal design power
(kW) (heavy load)
0.478 0.551 0.478 0.551 0.694 0.815
Thermal design power
(kW) (light load)
0.616 0.76 0.616 0.76 0.85 1.04
Air flow (CFM)
51.9 57.4 51.9 57.4 118.5 118.5
Overvoltage category
OVC III
Pollution degree
PD2
IP rating
IP20 (open type, for IEC products)
Type 1 (enclosed type, for UL products)