Technical Data
‑135‑
Table 7–4 Electrical specifications (three‑phase 380 V to 480 V) (T7 to T9 models)
Item
Specifications
Model: MD500Txxxxx‑PLUS
45G/
55P(B)
55G/
75P(B)
75G/
90P(B)
90G/110P
110G/
132P
132G/
160P
160G/
200P
Structure T7 T8 T9
Output
Power (kW) (heavy load)
45 55 75 90 110 132 160
Power (kW) (light load)
55 75 90 110 132 160 200
Rated output current (A)
(heavy load)
91 112 150 176 210 253 304
Rated output current (A)
(light load)
112 150 176 210 253 304 377
Output voltage Three‑phase 0 V to input voltage
Max. output frequency 599 Hz (editable through a parameter)
Carrier frequency
0.8 kHz to 8.0 kHz (automatically
adjusted according to the load
characteristics)
0.8 kHz to 6.0 kHz (automatically adjusted
according to the load characteristics)
Overload capacity
Heavy load (G‑type AC drive): 150% for 60s with rated current
Light load (P‑type AC drive): 110% for 60s with rated current
Input
Rated input current (A)
(heavy load)
89 106 139 164 196 240 287
Rated input current (A)
(light load)
111 143 167 198 239 295 359
Rated voltage/frequency Three‑phase 380 VAC to 480 VAC, 50/60 Hz
Voltage range
Allowable fluctuation: –15% to +10% (323 VAC to 528 VAC)
Frequency range
Allowable fluctuation: ±5% (47.5 Hz to 63 Hz)
Power capacity (kVA)
(heavy load)
81 97 127 150 179 220 263
Power capacity (kVA) (light
load)
102 131 153 181 219 270 328
Thermal
design
Thermal design power (kW)
(heavy load)
1.01 1.21 1.57 1.81 2.14 2.85 3.56
Thermal design power (kW)
(light load)
1.22 1.61 1.91 2.22 2.67 3.61 4.68
Air flow (CFM)
122.2 122.2 218.6 287.2 354.2 547 627
Overvoltage category
OVC III
Pollution degree
PD2
IP rating IP20 (open type, for IEC products)