Technical Data
142
Table 7–11 Electrical specifications (three‑phase 200 V to 240 V) (T9 to T12 models)
Item
Specifications
Model: MD500‑2Txxxxx‑PLUS
75G/90P 90G/110P 110G/132P 132G/160P 160G/200P 200G/220P
Structure T9 T10 T11 T12
Output
Power (kW) (heavy load)
75 90 110 132 160 200
Power (kW) (light load)
90 110 135 160 200 220
Rated output current (A)
(heavy load)
304 377 426 465 585 725
Rated output current (A)
(light load)
377 465 520 585 725 880
Output voltage Three‑phase 0 V to input voltage
Max. output frequency 599 Hz (editable through a parameter)
Carrier frequency
0.8 kHz to 6.0 kHz (automatically adjusted according to the load
characteristics)
Overload capacity
Heavy load (G‑type AC drive): 150% for 60s with rated current
Light load (P‑type AC drive): 110% for 60s with rated current
Input
Rated input current (A)
(heavy load)
287 365 410 441 565 687
Rated input current (A)
(light load)
359 456 507 559 708 840
Rated voltage/frequency Three‑phase 200 VAC to 240 VAC, 50/60 Hz
Voltage range
Allowable fluctuation: 15% to +10% (170 VAC to 264 VAC)
Frequency range
Allowable fluctuation: ±5% (47.5 Hz to 63 Hz)
Power capacity (kVA) (heavy
load)
263 334 375 453 517 629
Power capacity (kVA) (light
load)
334 375 453 517 629 716
Thermal
design
Thermal design power (kW)
(heavy load)
3.56 4.15 4.55 5.33 5.69 6.91
Thermal design power (kW)
(light load)
4.15 4.55 5.33 5.69 6.91 7.54
Air flow (CFM)
627 638.4 722.5 882 645 860
Overvoltage category
OVC III
Pollution degree
PD2
IP rating
IP20