5.4 Peripheral Electrical Components
5.4.1 Fuse, Contactor, and Circuit Breaker
To avoid electric shocks, do not power on the AC drive or operate peripherals immediately
after a fuse burns or a circuit breaker trips. Instead, wait at least a period of time specified
on the product warning label before further operations. Failure to comply will result in
product damage, several injuries, or even death.
To comply with EN 6180051 and UL61800‑5‑1 standards, install a fuse/circuit breaker
on the input side of the drive to prevent accidents caused by short circuit in the
internal circuit.
The following tables list recommended fuses and circuit breakers manufactured by
Bussmann.
Table 5–11 Selection of fuses, contactors, and circuit breakers (three phase 380‑480 V)
Structure Drive Model Fuse
Bussmann
Contactor Circuit Breaker
Rated Current
(A)
Model Rated Current
(A)
Rated Current (A)
T1 MD520‑4T0.4B(S) 5 FWP‑5B 9 4
MD520‑4T0.7B(S) 10 FWP‑10B 9 6
MD520‑4T1.1B(S) 10 FWP‑10B 9 6
MD520‑4T1.5B(S) 10 FWP‑10B 9 10
MD520‑4T2.2B(S) 15 FWP‑15B 12 13
MD520‑4T3.0B(S) 20 FWP‑20B 16 16
T2 MD520‑4T3.7B(S) 30 FWP‑30B 26 25
MD520‑4T5.5B(S) 40 FWP‑40B 26 32
T3 MD520‑4T7.5B(S) 60 FWP‑60B 38 50
MD520‑4T11B(S) 70 FWP‑70B 50 63
T4 MD520‑4T15B(S) 70 FWH‑70B 50 63
T5 MD520‑4T18.5(B)(S)
MD520‑4T18.5(B)(S)‑T
100 FWH‑100B 65 80
MD520‑4T22(B)(S)
MD520‑4T22(B)(S)‑T
125 FWH‑125B 80 80
T6 MD520‑4T30(B)(S) 125 FWH‑125B 80 100
MD520‑4T37(B)(S) 150 FWH‑150B 95 160

Table of Contents

Other manuals for Inovance MD520 Series