Electrical Design Guide
48
The protective grounding conductor must be a yellow/green cable comprised of
copper conductors. Do not connect the protective grounding conductor to a
switching device (such as a circuit breaker) in serial.
Ground the grounding terminal properly. Improper grounding will lead to device
malfunction or damage.
Do not connect the grounding terminal to the N terminal of the neutral wire of the
power supply.
It is recommended to install the drive to a conductive metal surface. Ensure the
whole conductive bottom of the drive is connected properly to the mounting face.
Tighten the grounding screw with specified tightening torque to prevent the
protective grounding conductor from being secured improperly.
Single-drive grounding
Installation of an individual drive:
R S T
Table 3–14 Single‑drive grounding
No.
Description
Input protection (fuse or circuit breaker) Connect the lower end of the
fuse to the filter.
Input power supply
Do not ground the DC bus terminal or the regenerative resistor terminal.
Connect the output PE terminal of the servo drive to the motor output
cable shield.
Connect the PE cable on the input power supply side to the input PE
terminal of the servo drive.
Ground the motor enclosure.
Three‑phase motor