100  Advisor Advanced ATSx000A(-IP) Installation and Programming Manual 
If set to No, the input needs both states to toggle between set and unset (pulse 
key switch). 
4.1.n.6.16 Key set 
 
The Key set option defines the zone as a key switch for area set. The following 
options are available: 
•  Off: the area set is not affected by the zone. 
•  Key part set: zone is a key switch for area part set. 
•  Key full set: zone is a key switch for area full set. 
4.1.n.6.17 Key unset 
 
If the Key unset option is set to Yes, the zone is a key switch that unsets an area. 
4.1.n.6.18 Technical full set 
 
If the Technical full set option is set to No, the technical alarms in this zone are 
disabled when the area is fully set. 
4.1.n.6.19 Technical unset 
 
If the Technical unset option is set to No, the technical alarms in this zone are 
disabled when the area is unset. 
4.1.n.6.20 Technical part set 
 
If the Technical part set option is set to No, the technical alarms in this zone are 
disabled when the area is partially set. 
4.1.n.6.21 Keypad LCD 
 
If the Keypad LCD option is set to Yes, when the zone activates, the zone name 
is displayed on the keypad LCD on all keypads, related to the area.