Advisor Advanced ATSx000A(-IP) Installation and Programming Manual  13 
Shielding 
The shielding of all shielded cables used in the system should only be connected 
at one side to one common earthing point in a building (see Figure 13 below). If a 
shielded databus cable is routed via more than one plastic device the shielding 
from incoming and outgoing cable must be connected. 
In case the IP connection is used, take care that the Ethernet FTP cable remains 
within a single building. Do make use of a proper router or switcher to isolate 
Ethernet cables between various buildings. 
Figure 13: System shielding 
(1)  Building 1 
(2)  Building 2 
(3)  Mains power with local earth 
(4)  Earth and shielding 
(5)  Mains power connector 
(6)  Advisor Advanced control panel 
(7)  System databus 
(8)  Device in plastic housing 
(9)  Device in metal housing 
 