EasyManua.ls Logo

Intertek FT Series - SECTION 6 Error Codes 6.1 Error Code Tables

Default Icon
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 70
SECTION 6 Error Codes
Error
Code
Error Code
Description
Possible Remedies
Recover
methods
10
Combustion
fault Flame has
Extinguished 8
(Eight) Times
Press the Power button to clear the Error Code. If Error happens again:
1. Monitor the gas pressure to the appliance while in operation. Ensure pressure is between 3.5” to 10.5” WC
(Nat. Gas) and 8” to 13” WC (Propane).
2. Check gas valve wire. Ensure connection is secure.
3. Check ame detection sensor. Ensure connections are secure. Normal operating settings are more than
2.5DC before ignition, less than 2.5DC after ignition.
4. Check exhaust and intake terminations for blockages. Also verify that intake, intake boot, blower and burner
housing is free of blockages and debris.
5. Assure that the ame is stable when lit. Conrm Flame stability by manually forcing the boiler into Low Fire
(see section 4.20) - Burner should not cycle on and off in low re. If burner cycles on/off during low re
operation adjust fuel/air mixture and conrm CO
2
values are within range for model and fuel type.
6. If the problem persists, contact technical support.
Hard
Lock
11
Ignition fault
Ignition has Failed
10 (Ten) Times
Press the Power button to clear the Error Code. If Error happens again:
1. Monitor the gas pressure to the appliance while in operation. Ensure pressure is between 3.5” to 10.5” WC
(Nat. Gas) and 8” to 13” WC (Propane).
2. Check gas valve wire. Ensure connection is secure.
3. Check ame detection sensor. Ensure connections are secure. Normal operating settings are more than
2.5DC before ignition, less than 2.5DC after ignition.
4. Check igniter transformer for proper connection.
5. Clean the spark igniter with steel wool to remove oxides. Ensure proper separation (3-4 mm).
6. Replace the spark igniter if damaged. Remove and inspect burner. If burner is damaged/blocked - replace
burner
7. Assure that the ame is stable when lit.
8. If the problem persists, contact technical support.
Hard
Lock
16
Water temperature
over-heating fault
Operating
Temperature
Sensor detects
Water Temperature
Greater than 203°F
(95°C)
Press the Power button to clear the Error Code.
If boiler is not piped Primary/Secondary it is likely the internal boiler pump is not able to move enough water thru
heat exchanger. If Error happens again:
1. Check if dip switch Max Fire setting is ON. Switches 6 and 7 should be OFF for normal operation.
2. Check if CH inlet pipe is blocked. Ensure there is enough water owing to the appliance.
3. Check Operating Temperature sensor at CH heat exchanger outlet. If resistance is zero, replace the sensor.
4. Verify operation of internal boiler pump by checking rotation of pump shaft. (Manually spin pump shaft by
inserting a at head screwdriver. You may need to remove a side panel knock-out for better access).
5. If the problem persists, contact technical support.
Hard
Lock
20
Blocked
condensate switch
fault
Press the Power button to clear the Error Code.
1. Check Condensate and main controller connections. Ensure all are secure.
2. Check Condensate sensor resistance. If resistance is zero, replace the switch.
3. Check Condensate hose. Ensure it is connected and in good condition.
4. Check condensate line and termination for blockages.
5. Check Vent Pipe for blockages.
6. If the condensate is “hard piped” in the eld, install a vent in the piping at a point higher than the
condensate trap.
7. If the problem persists, contact technical support.
Hard
Lock
28
Overheat
sensor fault
This Error Code will go away when CH temperature decreases. If Error happens again:
1. Check overheat temperature sensor. Ensure connections are secure.
2. Check overheat sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, contact technical support.
Soft Lock
29
Factory installed
Jumper missing
or not connected.
1. Check upper left plug on PCB board. Reconnect blue jumper wire part of this plug.
2. Press the Power button to clear the Error code. Error occurs when the blue wire inside the KI-I9CCWL plug
(upper left corner of PCB board) is shorted to ground or has a poor contact.
Hard
Lock
32
DHW outlet
sensor fault
This Error Code will go away when CH temperature decreases. If Error happens again:
1. Check DHW or CH temperature sensor. Ensure connections are secure.
2. Check DHW or CH sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, contact technical support.
Soft Lock
33
OP Water
temperature
sensor fault
6.1 Error Code Tables

Table of Contents