The FT Series Floor Standing, Heating Only Boiler
Page 75
Question Answer
The blower is still oper-
ating after the combus-
tion stops.
This is normal because the blower keeps operating for 1 minute to vent (exhaust) the
ue gas from the chamber once the combustion has stopped.
Temperature Rise
too Quickly
Occurs when supply water temperature in heat exchanger rises faster than 2°F per
second during the rst two minutes the burner is on. Automatically resets after a
few minute delay or using manual reset on control panel. See message displayed
TEMPERATURE SENSOR and follow procedure for loose connections.
Abnormal sounds come
from unit during opera-
tion.
A leak of combustion gas between sealed chamber and exhaust tube inside the unit.
Call a qualied service technician for evaluation.
Improper venting termination, make sure that the venting termination complies with
specication.
Check the supply gas pressure is sucient. Insucient gas pressure will cause unstable
burner ame and noise.
CH Temp drops lower
than expected before unit
re-res
Change Parameter 17:bo to 10 degrees F (5.5 degrees C)
SECTION 7 Trouble Shooting
7.1 Diagnostics