7.4. Macro Functions – Terminal Mode (P-12 = 0)
P-15 DI1 DI2 DI3 / AI2 DI4 / AI1 Diagram
0 1 0 1 0 1 0 1
0 STOP RUN
FWD REV
AI1 REF P-20 REF Analog Input AI1 1
1 STOP RUN AI1 REF PR-REF P-20 P - 21 Analog Input AI1 1
2 STOP RUN DI2 DI3 PR P-20 - P-23 P- 01 2
0 0 P-20
1 0 P- 21
0 1 P-22
1 1 P-23
3 STOP RUN AI1 P-20 REF E-TRIP OK Analog Input AI1 3
4 STOP RUN AI1 AI2 Analog Input AI2 Analog Input AI1 4
5 STOP RUN FWD
STOP
RUN REV
AI1 P-20 REF Analog Input AI1 1
^------FAST STOP (P-24)------^
6 STOP RUN
FWD REV
E-TRIP OK Analog Input AI1 3
7 STOP RUN FWD
STOP
RUN REV
E-TRIP OK Analog Input AI1 3
^------FAST STOP (P-24)------^
8 STOP RUN
FWD
REV DI3 DI4 PR 2
0 0 P-20
1 0 P- 21
0 1 P-22
1 1 P-23
9 STOP START FWD
STOP START REV
DI3 DI4 PR 2
^------FAST STOP (P-24)------^ 0 0 P-20
1 0 P- 21
0 1 P-22
1 1 P-23
10 (NO)
START
STOP (NC) AI1 REF P-20 REF Analog Input AI1 5
11 (NO)
START
FWD
STOP (NC) (NO)
START
REV
Analog Input AI1 6
^---------------------FAST STOP (P-24)---------------------^
12 STOP RUN FAST STOP
(P-24)
OK AI1 REF P-20 REF Analog Input AI1 7
13 (NO) START FWD
STOP (NC) (NO) START REV
KPD REF P-20 REF 13
^---------------------FAST STOP (P-24)---------------------^
14 STOP RUN DI2 E-TRIP OK DI2 DI4 PR 11
0 0 P-20
1 0 P- 21
0 1 P-22
1 1 P-23
15 STOP RUN P-23 REF AI1 Fire Mode Analog Input AI1 1
16 STOP RUN P-23 REF P-21 REF Fire Mode FWD REV 2
17 STOP RUN DI2 Fire Mode DI2 DI4 PR 2
0 0 P-20
1 0 P- 21
0 1 P-22
1 1 P-23
18 STOP RUN
FWD REV
Fire Mode Analog Input AI1 1
Analog and Digital Input Macro Configurations