Optidrive Plus 3
GV
Compact - User Guide
www.invertek.co.uk
5
2. Technical data
2.1. Environmental
Operational ambient temperature range : -10 … 60°C, Frost and condensation free
Storage ambient temperature range : -40 … 60°C
Maximum altitude : 2000m. Derate above 1000m : 1% / 100m
Maximum humidity : 95%, non-condensing
2.2. Rating tables
(kW)
Input
Current
or
MCB
(type
B)
Cable
Size
Output
Current
Output
Current 60
secs
Cable
Size
Cable
Length
OPC-1-12075-1K012 0.75 1 12.5 16 1.5 4.3 6.4 1 10
OPC-1-12150-1K012 1.5 2 19.3 25 4 7 10.5 1.5 10
(kW)
Input
Current
or
MCB
(type
B)
Cable
Size
Output
Current
Output
Current 60
secs
Cable
Size
Cable
Length
OPC-1-12075-1KB12 0.75 1 12.5 16 1.5 4.3 6.4 1 10
OPC-1-12150-1KB12 1.5 2 19.3 25 4 7 10.5 1.5 10
Input
Current
MCB
(type B)
Cable
Size
Output
Current
Output
Current 60
secs
Cable
Size
Motor
Cable
Length
OPC-1-14075-3K012 0.75 1 2.9 6 1 2.2 3.3 1 10
OPC-1-14150-3K012 1.5 2 5.4 6 1 4.1 6.1 1 10
Input
Current
MCB
(type B)
Cable
Size
Output
Current
Output
Current 60
secs
Cable
Size
Motor
Cable
Length
OPC-1-14075-3KA12 0.75 1 2.9 6 1 2.2 3.3 1 10
OPC-1-14150-3KA12 1.5 2 5.4 6 1 4.1 6.1 1 10