What to do if my Invertek Drives Optidrive ODP-2 Inverter has a fault when running?
- KKevin HensonAug 2, 2025
If your Invertek Drives Inverter is experiencing a fault during operation, consider these steps: * If operating in Vector mode, try reducing the speed loop gain. * Examine when the decimal points are flashing (indicating an overload) and either increase the acceleration rate or decrease the load. * Verify the motor cable length is within specified limits. Also, ensure the motor nameplate parameters are correctly entered. Check the motor and its wiring for any short circuits. If the problem occurs during deceleration, increase the deceleration ramp time or connect a suitable brake resistor. Check the incoming supply voltage and all connections to the drive.