Version 3.00 | Optidrive P2 User Guide | 41www.invertekdrives.com
P1-13 DI1 DI2 DI3 AI1 / DI4 AI2 / DI5
State 0 1 0 1 0 1 0 1 0 1
17 STOP
RUN FWD
STOP
RUN REV
DI3 DI4 Preset Speed E-TRIP OK
Off Off P2-01 REF
On Off P2-02 REF
Off On P2-03 REF
On On P2-04 REF
18 STOP
RUN FWD
STOP
RUN REV
DI3 DI4 Preset Speed DECEL P1-04 DECEL P8-11
Off Off P2-01 REF
On Off P2-02 REF
Off On P2-03 REF
On On P2-04 REF
19 STOP
RUN FWD
STOP
RUN REV
DI3 DI4 Preset Speed P1-12 REF PR-REF
Off Off P2-01 REF
On Off P2-02 REF
Off On P2-03 REF
On On P2-04 REF
20 STOP
RUN FWD
STOP
RUN REV
(NO)
INC SPD
(NO)
DEC SPD
P1-12 REF
1
P2-01-REF
21 (NO)
START
FWD
STOP
(NC) (NO)
START
REV
Analog Input AI1 P1-12 REF P2-01-REF
1) When P1-12 = 0 and P 1-13 = 10 or 20, the Motorised Pot / Keypad reference is automatically selected to be the Selected
Speed Reference.
7.3. Example Connection Schematics
P1-13 Setting : 1 4 11 14
+24V
DIN1
DIN2
DIN3
+10V
AIN1
0V
0V
AIN2
STO+
STO-
1
2
3
4
5
6
7
8
9
10
11
12
13
+24VDC +24VDC +24VDC +24VDC
Enable / Disable Enable / Disable Run Forward Run Forward
Reverse / Forward Reverse / Forward Run Reverse Run Reverse
P1-12 REF /
PR REF
P1-12 REF /
PR REF
P1-12 REF /
PR REF
P1-12 REF /
PR REF
+10 VDC +10 VDC +10 VDC +10 VDC
AIN 1 AIN 1 AIN 1 AIN 1
0 V 0 V 0 V 0 V
AOUT 1 AOUT 1 AOUT 1 AOUT 1
0 V 0 V 0 V 0 V
P2-01 /
P2-02 REF
DECEL P1-04 /
DECEL P8-11
P2-01 /
P2-02 REF
DECEL P1-04 /
DECEL P8-11
AOUT 2 AOUT 2 AOUT 2 AOUT 2
STO + STO + STO + STO +
STO - STO - STO - STO -
7
Control Terminal Functions