5. Electrical Power Wiring and Installation
5.1. Connection Diagram
Fuses /
Circuit
breaker
Install suitably rated fuses/Circuit breakers .
If an earth leakage detection device is used (e.g.ELCB/RCD), a type
B trip characteristic which is suitable for protecting equipment
with a DC component should be used, 1 device for multiple
drives should be avoided.
Isolator Ensure there is at least 30 seconds between each power-on.
Whenever possible use a motor that is designed for operation
from an inverter.
Ensure the voltage rating of the drive and motor match, special
care should be taken with dual voltage motors and that the
correct configuration has been set.
L1
L2
U
V
A1 : Red = Fault (refer to trip shown on remote keypad display)
Green = Healthy
A2 : Flashing = RJ45 Communication healthy
Power “on” indicator
Status Relay
+24V
DI 1
DI 2
DI 3/AI 2
+10V
AI 1
0V
AO1
0V
Modbus
+
Modbus -
RL1-A
RL1-B
1
2
3
4
5
6
7
8
9
10
11
Metal Back-plate (Earthed)
W
L3