Optidrive Compact-2 Engineering Guide Issue 07.docx
50
www.invertekdrives.com
11
Technical Data
11.8. Under / Over Voltage Trip Levels
The following levels are not user adjustable, and define the operating voltage levels of the drive and brake chopper circuit.
Drive Rated
Supply Voltage
Frame
Size
Drive Type
DC Bus Voltage Level (Volts DC)
Brake
Chopper
On
Brake
Chopper
Off
Under
Voltage
Trip
Minimum
Operating
(Inrush
Disabled)
Over
Voltage
Trip
100 115 Volts AC
FS1
Voltage Doubler
N/A
N/A
160
239
418
110 240 Volts AC
FS1
PFC
N/A
N/A
160
239
418
200 240 Volts AC
FS1
All
N/A
N/A
160
239
418
380 480 Volts AC
FS1
All
N/A
N/A
320
478
835
380 480 Volts AC
FS2
All
780
756
320
478
835
11.9. Automatic Switching Frequency Reduction
The switching frequency selected in P-17 will be automatically reduced based on the heatsink temperature according to the data in section 4.5
Maximum Permissible Heatsink Temperature. In addition, switching frequency is reduced under the following conditions:
11.9.1. Output Frequency based Effective Switching Frequency Reduction
At low output frequency, Effective Switching Frequency is automatically reduced. Hysteresis is applied to prevent continuous switching. The
operation is according to the following table:
P-17
32kHz
24kHz
16kHz
12kHz
8kHz
4kHz
Effective Switching Frequency increases
when Output Frequency exceeds
9.0Hz
7.0Hz
5.0Hz
3.0Hz
N/A
N/A
Effective Switching Frequency reduces
when Output Frequency reduces below
7.0Hz
5.0Hz
3.0Hz
1.0Hz
N/A
N/A
11.9.2. Output Current Based Effective Switching Frequency Reduction
Effective Switching Frequency is automatically reduced based on motor load current as follows:
All OPC-2-240095 models:
o If P-17 = 12kHz, 16 kHz, 24 kHz, Effective switching frequency is reduced to 8 kHz when motor current exceeds 10.45A (110%
of the drive rated current). Switching frequency will return to the value set in P-17 when motor current reduces below 7.6A
(80% of drive rated current)
o If P-17 = 32kHz, Effective switching frequency is reduced to 8 kHz when motor current exceeds 10.45A (110% of drive rated
current). Switching frequency changes to 24 kHz when motor current reduces below 7.6A (80% of drive rated current).
Switching frequency will return to the value set in P-17 when motor current reduces below 6.7A (70% of drive rated current)
All other models:
o Effective switching frequency is reduced to 8 kHz when motor current exceeds 140% of the drive rated current. Switching
frequency will return to the value set in P-17 when motor current reduces below 110% of drive rated current.
11.10. Electrical Rating Tables
Frame
Size
kW
HP
Input
Current
Fuse / MCB (Type B)
Maximum Cable Size
1
Output
Current
Non UL
UL
2, 3, 4
mm
AWG
A
110 - 240 (+ / - 10%) V 1 Phase Input, 230 Volt 3 Phase Output (Voltage Doubler) with Integrated PFC
1B
0.75
1
TBC
16
15
2.5
14
4.3
200 - 240 (+ / - 10%) V 1 Phase Input, 3 Phase Output
1A
0.37
0.5
TBC
TBC
N/A
2.5
14
TBC
1A
0.75
1
TBC
TBC
N/A
2.5
14
4.3
200 - 240 (+ / - 10%) V 1 Phase Input, 3 Phase Output with Integrated PFC
1B
1.5
2
8.3
16
15
2.5
14
TBC
380 - 480 (+ / - 10%) V 3 Phase Input, 3 Phase Output
1A
0.75
1
3.5
6
6
2.5
14
2.3
1A
1.5
2
5.6
10
10
2.5
14
4.1
2
2.2
3
TBC
10
10
2.5
14
5.8
2
4
5
TBC
16
15
2.5
14
9.5
Note
1. Cable sizes shown are the maximum possible that may be connected to the drive. Cables should be selected according to
local wiring codes or regulations applicable at the point of installation
2. Refer to the UL Online Certification Directory for a list of UL Recognised products, File Number E226333
3. The integral overload protection does not provide branch circuit protection. Branch circuit protection must be provided in
accordance with applicable local regulations and the National Electrical Code.
4. Fuse type : UL JDDZ Class J
5. Where permitted, equivalent circuit breakers may be used