Optidrive Compact-2 Engineering Guide Issue 07.docx
www.invertekdrives.com
45
9
Serial Communications
Modbus RTU Registers 25 - 28: Drive Serial Number
The drive serial number may be read using these four registers. The serial number has 11 digits, stored as follows:-
Register 28
Register 27
Register 26
Register 25
x
x
x
x
x
x
x
x
x
x
x
e.g.
Register 25
1
Register 26
1
Register 27
8745
Register 28
57
Drive Serial Number
5
7
8
7
4
5
0
1
0
0
1
Start Mode, Auto Restart & Fire Mode Configuration (P-30)
This parameter contains 3 values, stored as follows:-
High Byte
Low Byte
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Input Type
0: Constant
1: Momentary Start
Input Sense
0: Normally Closed (Open
Fire Mode)
1: Normally Open (Closed
Fire Mode)
Start Mode / Auto Restart as:-
0: Edge-r
1: Auto-0
2: Auto-1
3: Auto-2
4: Auto-3
5: Auto-4
6: Auto-5
DC Injection Configuration (P-32)
The parameter value is stored as a combined 16 bit word which is constructed as follows:-
High Byte
Low Byte
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
DC Injection Mode
0: DC Injection on Start
1: DC Injection on Stop
2: DC Injection on Start & Stop
DC Injection Duration: 1dp, e.g. 0 250 = 0.0 25.0s
Communications Configuration (P-36)
This Register entry contains multiple data entries, as follows:-
High Byte
Low Byte
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Trip Configuration
Baud Rate
Drive Address
Data values can be interpreted as follows:-
Drive Address
1 to 63
Baud Rate
Setting
Modbus RTU
CAN
0
115k2
500
1
115k2
500
2
9k6
500
3
19k2
500
4
38k4
500
5
57k6
500
6
115k2
500
7
115k2
125
8
115k2
250
9
115k2
500
10
115k2
1000
Trip Time Set-
up
0
Comms Loss Trip Disabled
1
30ms Watchdog, Trip on Comms Loss
2
300ms Watchdog, Trip on Comms Loss
3
1000ms Watchdog, Trip on Comms Loss
4
3000ms Watchdog, Trip on Comms Loss
5
30ms Watchdog, Ramp to Stop on Comms Loss
6
300ms Watchdog, Ramp to Stop on Comms Loss
7
1000ms Watchdog, Ramp to Stop on Comms Loss
8
3000ms Watchdog, Ramp to Stop on Comms Loss
Display Scaling (P-40)
The parameter value is stored as a combined 16 bit word which is constructed as follows:-
High Byte
Low Byte
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Display Scaling Source
0: Motor Speed
1: Motor Current
2: Analog Input 2 Signal
3: PI Feedback
Display Scaling Factor: 3dp, e.g. 0 16000 = 0.000 16.000