Set the switching threshold of the VFD:
0: Switch at zero frequency
1: Switch at the starting frequency
2: Switch after the speed reaches the stop speed
with a delay.
When the channel of running commands is
terminal control, the system detects the state of
the running terminal during power-on.
0: The terminal running command is invalid at
power-on. Even the running command is
considered as valid during power-on, the VFD
does not run and it keeps the protection state
until the running command is canceled and
enabled again.
1: The terminal running command is valid at
power-on. If the running command is considered
as valid during power-on, the VFD is started
automatically after the initialization.
Note: Exercise caution before using this
function. Otherwise, serious result may follow.
This function code determines the running state
of the VFD when the set frequency is lower than
the lower-limit one.
0: Run at the frequency lower limit
1: Stop
2: Sleep
The VFD will coast to stop when the set
frequency is lower than the lower-limit one.if the
set frequency is above the lower limit one again
and it lasts for the time set by P01.20, the VFD
will come back to the running state automatically.