Goodrive300-01 inverter for air compressor Product overview
-9-
2.5 Wiring diagram
2.5.1 Terminal arrangement
2.5.2 Terminal instruction
RO1 relay output, RO1A NO, RO1C common terminal
Contact capacity: 3A/AC250V, 1A/DC30V
RO2 relay output, RO2A NO, RO2C common terminal
Contact capacity: 3A/AC250V, 1A/DC30V
RO3 relay output, RO3A NO, RO3B NC, RO3C common terminal
Contact capacity: 3A/AC250V, 1A/DC30V
RO4 relay output, RO4A NO, RO4B NC, RO4C common terminal
Contact capacity: 3A/AC250V, 1A/DC30V
+10V reference null potential
1. Input range: AI1/AI2 voltage and current can be chosen: 0~10V/0~20mA; AI1
can be shifted by J3; AI2 can be shifted by J4; AI3: -10V~+10V
2. Input impedance: Voltage input: 20kΩ; current input: 500Ω
3. Resolution: 5mV when 10V corresponds to 50Hz
4. Deviation ±1%, 25°C
1. Output range: 0~10V or 0~20mA; the voltage or the current output depends
on the jumper; AO1 can be shifted by J1; AO2 can be shifted by J2
2. Deviation ±1%, 25°C
1. Input interface of PT100 temperature detection signal
2. Range of temperature detection: -30~120°C , detection precision: 1°C
3. PTA and PTB are input terminals of sampling analog signal, PTC is
reference signal input terminal
4. PTB and PTC terminals are short circuited inside PCB, removing the need
for external short circuit cap.