Goodrive300-01 inverter for air compressor Communication protocol
-86-
The address of function code occupies 2 bytes with the high bit is in the front and the low bit in behind.
The range of high and low byte is: high byte—00~ffH; low byte—00~ffH. The high byte is the group
number before the radix point of the function code and the low byte is the number after the radix point.
But both the high byte and the low byte should be changed into hex. For example P05.06, the group
number before the radix point of the function code is 05, then the high bit of the parameter is 05, the
number after the radix point 06, then the low bit of the parameter is 06, then the function code
address is 0506H and the parameter address of P10.01 is 0A01H.
A.2.4.2 The address instruction of other Modbus function
This part is the address definition for communication data. It is used to control inverter operation,
obtain inverter state information as well as relevant inverter parameter setting.
Communication control
command
0006H:coast to stop (emergency stop)
The address of the
communication setting value
Communication setting frequency
(0~Fmax (unit: 0.01Hz))
PID reference, range (0~1000, 1000
corresponds to100.0% )
PID feedback, range (0~1000, 1000
corresponds to100.0% )
Torque setting value (-3000~3000,
1000 corresponds to the 100.0% of the
rated current of the motor)
The upper limit frequency setting during
forward rotation (0~Fmax (unit:
0.01Hz))
The upper limit frequency setting during
reverse rotation (0~Fmax (unit:
0.01Hz))
The upper limit torque of electromotion
torque (0~3000, 1000 corresponds to
the 100.0% of the rated current of the
motor)
The upper limit torque of braking torque
(0~3000, 1000 corresponds to the