0: Decelerate to stop: after the stop command
becomes valid, the inverter decelerates to decrease
the output frequency during the set time. When the
frequency decreases to P01.15, the inverter stops.
1: Coast to stop: after the stop command becomes
valid, the inverter ceases the output immediately.
And the load coasts to stop at the mechanical inertia.
The starting frequency of stop braking: the inverter
will carry on stop DC braking when the frequency is
arrived during the procedure of decelerating to stop.
The waiting time of stop braking: before the stop DC
braking, the inverter will close output and begin to
carry on the DC braking after the waiting time. This
function is used to avoid the overcurrent fault caused
by DC braking when the speed is too high.
Stop DC braking current: the DC brake added. The
stronger the current, the bigger the DC braking
effect.
The braking time of stop braking: the retention time
of DC brake. If the time is 0, the DC brake is invalid.
The inverter will stop at the set deceleration time.