EasyManua.ls Logo

INVT GD300-01-7R5G-4

INVT GD300-01-7R5G-4
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive300-01 inverter for air compressor Function parameters
-22-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
The setting range: 0.00~100.00 (only valid when
P01.16=1)
P01.18
Terminal
running protection
when powering on
When the run commands are controlled by the
terminal, the system will detect the state of the
running terminal during powering on.
0: The terminal run command is invalid when
powering on. Even the run command is detected to
be valid during powering on, the inverter will not run
and the system keeps in the protection state until the
run command is canceled and enabled again.
1: The terminal run command is valid when powering
on. If the run command is detected to be valid during
powering on, the system will start the inverter
automatically after the initialization.
Note: This function should be selected with
cautions, or serious result may follow.
0
P01.19
Action if running
frequency< lower
limit frequency
(valid >0)
This function code determines the running state of
the inverter when the set frequency is lower than the
lower-limit one.
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
The inverter will coast to stop when the set
frequency is lower than the lower-limit one; if the set
frequency is above the lower-limit one again and it
lasts for the time set by P01.20, the inverter will
restore to the running state automatically.
0
P01.20
Hibernation
restore delay time
This function code determines the hibernation delay
time. When the running frequency of the inverter is
lower than the lower limit one, the inverter will pause
to stand by.
0.0s

Table of Contents

Related product manuals