Goodrive300-01 inverter for air compressor Function parameters
-32-
Detailed instruction of parameters
T
f
0.1
Flux weakening coefficient
of motor
1.0
2.0
Min. flux weakening limit of
motor
Function code P03.22 and P03.23 are effective at
constant power. The motor will enter into the
weakening state when the motor runs at rated
speed. Change the weakening curve by modifying
the weakening control coefficient. The bigger the
weakening control coefficient is, the steeper the
weak curve is.
P03.22 is only valid for vector control mode 1.
The setting range of P03.22: 0.1~2.0
The setting range of P03.23: 10%~100%
P03.24 sets the maximum voltage of the inverter,
which is dependent on the site situation.
The setting range: 0.0~120.0%
Carry out motor pre-excitation when the inverter
starts up. Build up a magnetic field inside the inverter
to improve the torque performance during the
starting process.
The setting range: 0.000~10.000s
Flux weakening
proportional gain
0~4000
Note: P03.24~P03.26 are invalid for vector
control mode 1.
Vector control
speed display
0: Display the actual value
1: Display the setting value
Start pull in total
current
Coefficient of
inductance
The function codes define the V/F curve of
Goodrive300- 01 series motors 1 to meet the need of
different loads.