When P04.00 =1, the user can set V/F curve through
P04.03~P04.08.
V/F is generally set according to the load of the
motor.
Note:V1 < V2 < V3,f1 < f2 < f3. Too high low
frequency voltage will cause overheat or even
burnout of the motor and overcurrent stall or
protection of the inverter.
The setting range of P04.03: 0.00Hz~P04.05
The setting range of P04.04: 0.0%~110.0% (the
rated voltage of motor 1)
The setting range of P04.05: P04.03~ P04.07
The setting range of P04.06: 0.0%~110.0% (the
rated voltage of motor 1)
The setting range of P04.07: P04.05~ P02.02 (the
rated frequency of motor 1) or P04.05~ P02.16 (the
rated frequency of motor 1)
The setting range of P04.08: 0.0%~110.0% (the
rated voltage of motor 1)