Goodrive300-01 inverter for air compressor Function parameters
-48-
Detailed instruction of parameters
clear the set value of UP/DOWN.
5: Coast to stop. Press QUICK/JOG to coast to stop.
6: Shift the reference manner of run commands.
Press QUICK/JOG to shift the reference manner.
7: Quick commissioning mode (commissioning
according to the non-factory parameters)
Note: Press QUICK/JOG to shift between forward
rotation and reverse rotation, the inverter does
not remember the state after shifting during
powering off. The inverter will run in the
direction set according to P00.13 during next
powering on.
QUICK/JOG
shifting sequence
selection
When P07.02=6, set the shifting sequence of run
command channels.
0: Keypad control→terminals control
→communication control
1: Keypad control←→terminals control
2: Keypad control←→communication control
3: Terminals control←→communication control
STOP/RST stop
function selection
The valid selection of STOP/RST stop function,
STOP/RST is valid in any state for the fault reset.
0: Only valid for the keypad control
1: Both valid for keypad and terminals control
2: Both valid for keypad and communication control
3: Valid for all control modes
Parameters
selection 1 for
running state
0x0000~0xFFFF
BIT0: running frequency (Hz on)
BIT1: set frequency (Hz flickering)
BIT2: bus voltage (Hz on)
BIT3: output voltage (V on)
BIT4: output current (A on)
BIT5: running rotation speed (rpm on)
BIT6: output power (% on)
BIT7: output torque (% on)
BIT8: PID reference (% flickering)
BIT9: PID feedback value (% on)
BIT10: input terminals state
BIT11: output terminals state
BIT12: torque set value (% on)