Goodrive300-01 inverter for air compressor Function parameters
-59-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
flux braking, while the cooling of the stator is more
effective than the rotor.
P08.51
Input power factor
of the inverter
This function code is used to adjust the displayed
current of the AC input side.
Setting range: 0.00~1.00
0.56
P09 Group PID control
P09.00
PID reference
source
When the frequency command selection (P00.06,
P00.07) is 7 or the voltage setting channel selection
(P04.27) is 6, the running mode of the inverter is
procedure PID control.
The parameter determines the target reference
channel of procedure PID.
0: Keypad (P09.01)
1: AI1
2: AI2
3: AI3
4: HDI
5: Multi-step speed
6: MODBUS communication
7: Reserved
8: Reserved
9: Reserved
10: Special pressure setting for air compressor
The setting target of procedure PID is a relative one,
100% of the setting equals to 100% of the response
of the controlled system.
The system is calculated according to the relative
value (0~100.0%).
Note: Multi-step speed reference, it is realized by
setting P10 group.
0
P09.01
Keypad PID
preset
When P09.00=0, set the parameter whose basic
value is the response value of the system.
The setting range: -100.0%~100.0%
0.0%
P09.02
PID feedback
source
Select the PID feedback channel by the parameter.
0: AI1
1: AI2
2: AI3
3: HDI
4: MODBUS communication
0