Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-170-
UP terminal
frequency
incremental
integral rate
DOWN terminal
frequency
decremental
change rate
Action selection
for frequency
setup during
power down
0x000–0x111
Ones place: Action selection at power-off during
frequency adjusting through digitals.
0: Save the setting at power-off.
1: Clear the setting at power-off.
Action selection at power-off during frequency
adjusting through Modbus/Modbus TCP
communication
0: Save the setting at power-off.
1: Clear the setting at power-off.
Hundreds place: Action selection at power-off
during frequency adjusting through DP
communication
0: Save the setting at power-off.
1: Clear the setting at power-off.
High bit of initial
value of power
consumption
Set the initial value of power consumption.
Initial value of power
consumption=P08.48×1000+ P08.49
Setting range of P08.48: 0–59999 kWh (k)
Setting range of P08.49: 0.0–999.9 kWh
Low bit of initial
value of power
consumption
This function code is used to enable flux braking
function.
0: Invalid
100–150: The larger the coefficient, the stronger
the brake intensity
The VFD enables motor to decelerate quickly by
increasing the motor flux which converts energy
generated during braking into thermal energy.
The VFD monitors motor state continuously
even during flux braking, thus flux braking can
be applied in motor stop or used to change
motor speed. The flux braking also carries the
following advantages.
1) Brake immediately after sending stop
command, removing the need to wait for flux to
attenuate.
2) Better cooling effect. During flux braking, the