Goodrive350 IP55 High-ingress Protection Series VFD Troubleshooting
-253-
port is damaged, if yes,
replace the insertion port
after power down
[65] Communication timeout
occurred to the expansion
card in card slot 3
There is no data
transmission in interfaces
of card slot 3
Confirm whether the
expansion card inserted can
be supported;
Stabilize the expansion card
interfaces after power
down, and confirm whether
fault still occurs at next
power-on;
Check whether the insertion
port is damaged, if yes,
replace the insertion port
after power down
[29] PROFIBUS card
communication timeout fault
There is no data
transmission between the
communication card and
the host computer (or
PLC)
Check whether the
communication card wiring
is loose or dropped
[30] Ethernet card
communication timeout fault
There is no data
transmission between the
communication card and
the host computer
Check whether the
communication card wiring
is loose or dropped
[31] CANopen card
communication timeout fault
There is no data
transmission between the
communication card and
the host computer (or
PLC)
Check whether the
communication card wiring
is loose or dropped
[57] PROFINET card
communication timeout fault
There is no data
transmission between the
communication card and
the host computer (or
PLC)
Check whether the
communication card wiring
is loose or dropped
[66] EtherCAT card
communication timeout fault
There is no data
transmission between the
communication card and
the host computer (or
PLC)
Check whether the
communication card wiring
is loose or dropped
[67] BACNet card
communication timeout fault
There is no data
transmission between the
communication card and
the host computer (or
PLC)
Check whether the
communication card wiring
is loose or dropped
[68] DeviceNet card
communication timeout fault
There is no data
transmission between the
communication card and
the host computer (or
PLC)
Check whether the
communication card wiring
is loose or dropped