Goodrive350 series high-performance multi-function inverter Chapter 5
-117-
Functio
n code
Name
Detailed parameter description
Default
value
40: Safe torque off (STO)
41: Channel H1 safety circuit exception
(STL1)
42: Channel H2 safety circuit exception
(STL2)
43: Channel H1 and H2 exception (STL3)
44: Safety code FLASH CRC check fault
(CrCE)
55: Repetitive extension card type fault
(E-Err)
56: Encoder UVW loss fault (ENCUV)
5758: Reserved
59: Motor over-temperature fault (OT)
60: Card slot 1 card identification failure
(F1-Er)
61: Card slot 2 card identification failure
(F2-Er)
62: Card slot 3 card identification failure
(F3-Er)
63: Card slot 1 card communication
timeout fault (C1-Er)
64: Card slot 2 card communication
timeout fault (C2-Er)
65: Card slot 3 card communication
timeout fault (C3-Er)
P07.33
Running frequency of present fault
0.00Hz
P07.34
Ramps reference frequency of present fault
0.00Hz
P07.35
Output voltage of present fault
0V
P07.36
Output current of present fault
0.0A
P07.37
Bus voltage of present fault
0.0V
P07.38
Max. temperature of present fault
0.0°C
P07.39
Input terminal state of present fault
0
P07.40
Output terminal state of present fault
0
P07.41
Running frequency of the last fault
0.00Hz
P07.42
Ramps reference frequency of the last fault
0.00Hz
P07.43
Output voltage of the last fault
0V
P07.44
Output current of the last fault
0.0A
P07.45
Bus voltage of the last fault
0.0V
P07.46
Max. temperature of the last fault
0.0°C