IRMA MATRIX Door Clear option | Mounting and operating instructions
released
3 Active Door Clear zone 4 Sensor´s field of view
2 Mounting IRMA MATRIX
2.1 Placing the IRMA MATRIX sensor
In addition to the installation instructions for CAN and Ethernet wiring, please note the
following points when placing the sensor especially for Door Clear:
• sensor tilt around the x-axis
1
must not exceed 3°.
• sensor must be between 5 - 20 cm away from the door along the y-axis
2
and
• should be placed above and in the middle of the function area.
Non-observance of these points can lead to malfunction of Door Clear!
2.2 Connection via Ethernet
For a 2-door bus (middle door: approx. 1.25m x 2.10m) with two IRMA MATRIX sensors, for
example, install via Ethernet as follows: follow the instructions in the document
KDIA_IRMA-MATRIX_R2_Installationsanleitung-ETH_1.5, available at:
https://www.irisgmbh.de/technische-dokumente/irma-matrix/. Fig. 2
shows the simplified
Door Clear signal chain for sensor installation via Ethernet.
1
x-plane = driving direction, y-plane = entry and exit direction, z-plane = vertical direction (up/down)
2
ibid.