INSTALLER SETUP MENU
SELECTING LOW BALANCE POINT OPTION
Menu 16 allows you to select a low balance point setting when the thermostat is
configured for Heat Pump or Dual Fuel and an outdoor sensor is used. When the
outdoor temperature falls below the balance point setting, the compressor is
locked out and only auxiliary electric heat or dual fuel furnace is used for heating.
The factory default is . Touch the or arrows to select a lowOFF UP DOWN
balance point setting.
Adjustable from OFF, 1° to 77°F
Remote outdoor sensor must be used