3.6.3 Testing the Connection
OncethepowerpackhasbeenwiredtotheAquaLinkRSControlSystemorPDA,followthesestepstotestthe
connection:
1. TurnonthepowerpackandtheAquaLinkRSControlSystemorPDA.
2. Wait about 20 seconds. If the connection was successful, a Ŧ symbol will appear in the top right corner of the
power pack display.
NOTE: Ifthepowerpackdoesnotconnecttothecontroller,turnthepowerofftobothdevicesandrepeatsteps1
and2.Ifthepowerpackstilldoesnotconnecttothecontroller,re-checkthewiringconnections(seeSection
3.6.2)andthecontrollersettingonthepowerpack(seeSection3.6.1).
Figure 21. Communication Wiring between Power Pack and AquaLink RS Control System or PDA Network
Jandy
Power Center
Power Pack
OPTIONAL
4 3 2 1
RED
BLK
YEL
GRN
Red, 4-Pin
Terminal Bar
RED
GRN
YLW
BLK
B
A
0V
POS
RED
BLK
7. TheJandy®AquaLink®
RSorPDAandpowerpack
useafour(4)wireconnectiontocommunicateandcanbe
wiredupto500feetapart.Anyoutdoorratedfourconductorcable,minimum22AWG,canbeused.Locatethe
appropriate screw terminals on the circuit board and wire the power pack
totheAquaLink
RSorPDAred4-pin
terminal bar (see Figure 21).
NOTE ThescrewterminalsontheAquaLinkRSorPDAareremovabletoaidininstallation.