UMG 604
Default
Add Name Setting range Units setting
100 Automatically get TFTP configuration file 0 .. 9999 - 0
0 = switched off
x = file number
101 TFTP error handling 0 .. 1 - 0
0 = In the event of an error the
Configuration menu appears
in the UMG604.
1 = In the event of an error the
does NOT switch to the
Configuration menu of the UMG604.
110 Current transformer circuit (L1 .. L3) 0 .. 1 - 0
0 = three current transformers
1 = two current transformers (Aron circuit)
111 Voltage measurement system configuration 0 .. 1 - 0
0 = three-phase 4-conductor system
1 = three-phase 3-conductor system
112 Deletes all real and apparent energy meters 0 .. 1 - 0
and S0-counters (1 = delete)
113 Deletes all reactive energy meters (1 = delete) 0 .. 1 - 0
114 Resets all minimum and maximum values 0 .. 1 - 0
(1 = reset)