73
UMG 604
Default
Add Name Setting range Units setting
200 Device address, modbus/profibus 1 .. 255 1
201 Baud rate, RS232 0 .. 4 4
0 = 9600 bit/s
1 = 19200 bit/s
2 = 38400 bit/s
3 = 57600 bit/s
4 = 115200 bit/s
202 Baud rate, RS485 0 .. 5 4
0 = 9600 bit/s
1 = 19200 bit/s
2 = 38400 bit/s
3 = 57600 bit/s
4 = 115200 bit/s
5 = 921600 bit/s
203 RS485, mode 0 .. 6 0
0 = modbus RTU/slave
1 = modbus RTU/master
2 = gateway transparent
5 = BACnet MS/TP (optional)
204 RS232, mode 0 .. 6 0
0 = modbus RTU/slave
3 = Debug
6 = SLIP
(only for internal use)