P117 Initialization of parameters
SettingRange:0-8Unit:1
Explanation: 8: Initialization of parameters
When the parameter setup is not proper or when false running leads to improper
setup of parameter, you can set P117 at 08 to restore all parameters to the
Factory Setting, and then you can set them again according to actual need.
Attention: when locked up of parameters is valid, that is when P118=1, you
cannot carry out initialization of parameters and change them. Please unlock
first, and then set these parameters.
Factory Setting: 0
P118 Initialization of parameters
SettingRange:0-1Unit:1
Explanation: 0: unlocked
1: Locked
You can lock the parameter by P118 to prevent unexpected change of the
inverter setup.
When P118 is valid, all the other parameters except P100 (main frequency
setting) cannot be changed.
Factory Setting: 0
Group P2: Parameters of basic applications
P200 Start mode selection
SettingRange:0-1Unit:1
Explanation: 0: Start at start frequency
1: Tracing start
There are two start modes for FC100 series inverter. You can choose from the
two by setup of parameter P200 and the condition of machinery.
0: Start at start frequency
Most loads do not have special requirement in start. Inverter output from the start
frequency.
Factory Setting: 0
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Janson Controls FC100-2S-0.7G and is the answer not in the manual?

Janson Controls FC100-2S-0.7G Specifications

General IconGeneral
BrandJanson Controls
ModelFC100-2S-0.7G
CategoryController
LanguageEnglish

Related product manuals