88
Default value 0.3s
PID integral time
P608
Setting Range:0~200.0s Unit:0.1
For deviation step input, time(Ti) required for only the integal (I) action to
provide the same manipulated variable as that for the proportional (P) action.
As the integral time decreases, the set point is reached earlier but hunting
occurs more easily.
Default value 0
PID differential time
P609
Setting Range:0.0~20.0 Unit:0.01
For deviation lamp input, time (Td) required for providing only the manipulated
variable for the proportional (P) action. As the differential time increases,
greater response is made to a deviation change.
Default value 0.1
PID differential time
P610
Setting Range:0.0~1.0HZ Unit:0.01
PID is figured out once every 10ms. Frequency increment will be figured out (
FHz) every time. While frequency increment is more than value of P610 in
maximum of frequency increment, P610 will work.
Default value 0.0
PID standby frequency
P611
Setting Range:0.0~120.0HZ Unit:0.01
P611 PID standby frequency.
P611 must reach minimum frequency in PID standby. When running frequency
is less than value of P610 standby duration will begin counting.
P612 PID standby duration.
When running duration of inverter is more than standby frequency the value
(standby duration) of P612, the inverter will be standby. Then stop output, and
disconnect with PID, but monitor the feedback of P613PID.
P613: PID wake-up value.
When the inverter detects that feedback value less than wake-up value (P613),
PID function will be taken action, and then inverter will start.
Default value 10.0
PID standby duration
P612
Setting Range:0.0~200.0HZ Unit:0.1
Default value 0.0%
PID wake-up value
P613
Setting Range:0.0~100%
6